CU2-15 -
Features
Features
Suitable for built-in installation
Air tightness in accordance with EN 1751: class B (class C in option)
Tested in accordance with EN1366-2 up to 1500 Pa
Operating mechanism outside the wall
Maintenance-free
For indoor use
Operating temperature: max. 50°C
Intermediate dimensions on request
Suitable for installation in rigid wall
Components
Connection flange PG30
Casing made of refractory material
Damper blade
Operating mechanism
Sealing cold smoke
Blade bumper
Intumescent strip
Transmission with locking (open/closed)
Fusible link
Product identification